Коды ошибок рефрижераторных установок Mitsubishi TDJS Series.

Коды ошибок рефрижераторных установок Mitsubishi TDJS Series.

Mitsubishi Transport Refrigeration Unit TDJS Series.

List of alarm codes.

Alarm Code Trouble Countermeasure Alarm Lamp Unit Condition
E003 Magnet clutch fuse break Magnet clutch fuse F2* is blown. Inspect and replace if necessary the fuse F2* in the control box On Unit stops
E006 Load drive circuit fuse break Load power supply relay fuse F7* is blown.
Inspect and replace if necessary the fuse F7* in the control box
On Unit stops
E010 HP abnormally high High-pressure switch has tripped

(1) Check if the condenser fan is running. If it is not, check the fuse F3* – or for disconnected wires in the control box

(2) Inspect if the condenser coil is fouled with dirt or mud. If it is, wash it with a soft brush and water

On Unit stops
E013 Td abnormally high Discharge gas temperature is abnormal. Check for bubbles in the sight glass. If bubbles are observed, ask a service shop for inspection On Unit stops
E014 Refrigerant shortage Refrigerant quantity is insufficient. Ask a service shop for inspection On Unit stops
E016 LPT failure Broken wire or short-circuit on the low-pressure sensor. Ask a service shop for inspection Blinking Unit operation continues
E017 HPT failure Broken wire or short-circuit on the high-pressure sensor. Ask a service shop for inspection Blinking Unit operation continues
E040 DCS2 shortcircuit (Abnormal stop output) Short-circuit on the abnormal stop output circuit. Ask a service shop for inspection. Ask a service shop for inspection Blinking Unit operation continues
E041 DCS1 shortcircuit (Operation output) Short-circuit on the operation output circuit. Ask a service shop for inspection. Ask a service shop for inspection Blinking Unit operation continues
E042 DCS3 shortcircuit (Out of range inside container) Short-circuit on the out of range inside container temperature output circuit. Ask a service shop for inspection Blinking Unit operation continues
E050 TH sensor failure Lo (*1). Short-circuit or poor connector connection on the inside container temperature sensor. Ask a service shop for inspection On, or blinking if setting temperature is lower than -10 ˚C Unit stops

(Or continuous cooling operation if setting temperature is lower than -10 ˚C.)

Hi (*1). Short-circuit on the inside container temperature sensor. Ask a service shop for inspection
E057 EVT sensor failure Broken wire or short-circuit on the evaporator exit temperature sensor. Ask a dealer for inspection Blinking Unit operation continues
E063 Td sensor failure Broken wire or short-circuit on the discharge gas temperature sensor at the engine side Ask a dealer for inspection Blinking Unit operation continues
E067 Td sensor failure (Motor side) Broken wire or short-circuit on the discharge gas temperature sensor at the motor side Ask a service shop for inspection Blinking Unit operation continues
E099 Controller communication failure Cabin controller cannot communicate properly. Ask a service shop for inspection On Unit stops
E101 Evaporator fan motor fuse break Evaporator fan motor fuse F1* is blown. Inspect and replace if necessary the fuse F1* in the control box. In case of 2-compartment model, if the evaporator fan motor fuse at second compartment is abnormal, inspect and replace if necessary the fuse F4* in the control box Blinking Unit operation continues
E102 Condenser fan motor fuse break Condenser fan motor fuse F3* is blown. Inspect and replace if necessary the fuse F3* in the control box Blinking Unit operation continues
E104 Drain hose heater fuse break Drain hose heater fuse F6* is blown. Inspect and replace if necessary the fuse F6* in the control box Blinking Unit operation continues
E160 Economizer SV shortcircuit (TDJS70*ZE only) Short-circuit on the economizer solenoid valve SV6 circuit. Ask a service shop for inspection Blinking Unit operation continues
E161 Economizer SV shortcircuit Short-circuit on the fluid line solenoid valve SV5F circuit. Ask a service shop for inspection On Unit stops
E163 Hot gas line SV shortcircuit Short-circuit on the hot gas solenoid valve SV1 circuit. Ask a service shop for inspection Blinking Unit operation continues
E167 Condenser outlet SV shortcircuit Short-circuit on the condenser exit solenoid valve SV3 circuit. Ask a service shop for inspection On Unit stops
E168 Liquid bypass SV shortcircuit Short-circuit on the fluid bypass solenoid valve SV2 circuit. Ask a service shop for inspection Blinking Unit operation continues

* – Indicates the smallest digit of fuse No.

*1 – Lo or Hi is indicated on the temperature display.

– In case of 2-compartment model, which of the parts that controls compartment is faulty is indicated with the A or B compartment operation indicator.